9 9800/9820 pump dispenser, Requirements, Cpu board – Gasboy CFN Site Controller User Manual
Page 66: Led indicators, Jumpers

58
9800/9820 Pump Dispenser
Pump Interface Manual v1.3
Gasboy CFN Series
03/20/03
9
9800/9820 Pump Dispenser
Requirements
•
RS-485 PCB is required for all CFNs (1-3).
•
Pulser Interface PCB is required for Series 1000, System ‘A’, or other outside card sys-
tems (i.e. Petrovend).
•
C06394 CPU will work in place of any of the 7 other versions.
•
C06397 power supply will work in place of other 3 versions.
CPU Board
LED Indicators
Jumpers
Jumper K1 is set according to the size of the RAM IC in socket U19. At this time, only the 2K
size is being used:
LED
Function
L1
AUTH1 - side 1 AC authorization present
L2
SLOW1 - side 1 slow flow solenoid
L3
FAST1 - side 1 fast flow solenoid
L4
SUBM1 - side 1 submersible starter relay
L5
AUTH2 - side 2 AC authorization present
L6
SLOW2 - side 2 slow flow solenoid
L7
FAST2 - side 2 fast flow solenoid
L8
SUBM2 - side 2 submersible starter relay
L9
PUL1A - side 1 pulser, channel A
L10
PUL1B - side 1 pulser, channel B
L11
HAND1 - side 1 handle switch
L12
PUL2A - side 2 pulser, channel A
L13
PUL2B - side 2 pulser, channel B
L14
HAND2 - side 2 handle switch
RAM
Jumper Pins
2K
across 2 and 3
8K
across 1 and 2