Pump Interface Manual v1.3

Gilbarco Interface Unit

29

03/20/03

Gasboy CFN Series

Front Panel LEDs

L1 L12
o o o o o o o o o o o o

CPU

o o o

Current Loop PCB

DC BOK BAD

Interface Board

Site Controller Configuration

Site Controller I

Site Controller I version 4.0 software and above will work with Gilbarco pumps.

Normally the Site Controller I is configured at the factory for the pump types. The pump types
are configured at TABLE 24, OFFSET 18+(PMP#-1)x4. Refer to the Site Controller I Technical
Manual
to help understand the following CONFIGS.

a) 2 sided, 1 hose per pump. Byte = 64

b) 1 sided, 1 hose per pump. Byte = 74
c) 2 sided, 2 hose per pump. Byte = 65
d) 1 sided, 2 hose per pump. Byte = 75
e) 2 sided, 3 hose per pump. Byte = 66
f) 1 sided, 3 hose per pump. Byte = 76

Note: SC I will not work with multi hose unit.

Lamp

Indication

L1

transmit data on CRIND 422/485 port

L2

receive data on CRIND 422/485 port

L3

transmit data on 422/485 loop #1

L4

receive data on 422/485 loop #1

L5

dead man timer refresh

L6

current loop power enabled

L7

current loop #1 active if flashing

L8

current loop #2 active if flashing

L9

program crash code bit 1

L10

program crash code bit 2

L11

program crash code bit 3

L12

program crash code bit 4

DC

DC 5V power OK (green)

BOK

battery OK (green)

BAD

battery bad (red)

Jumper

Function and/or Normal Setting

K1

Baud rate clock source; must be installed in position 1.

K2

Battery backup enable. Boards should be stored with this
jumper out; it should be installed at assembly time. Lamp
BAD will light if K2 is omitted.