6 wayne, The wayne ec cabinet, Scii cabling and port jumper configuration – Gasboy CFN Site Controller User Manual
Page 48: Wayne

40
Wayne
Pump Interface Manual v1.3
Gasboy CFN Series
03/20/03
6
Wayne
The FRAMOS.BIN must have the Wayne pump driver installed. The SCII must have v1.0K or
above for Wayne. For CATS, the SCII must have v2.1 or above.
All CFN3 versions will work with Wayne pumps and CATS.
The Wayne EC Cabinet
Requirements for the Wayne EC Cabinet and Data Distribution Box:
Rev. 49 2400 CPU board. This unit must be equipped with a PIB/Plus board also
available from Wayne. All dispenser wiring to/from the Wayne 2400 Controller should be
done according to Wayne Installation instructions.
Notes:
•
Older EC Cabinets can be upgraded to a Rev. 49 CPU and PIB/Plus board. All Wayne
Electronic dispensers except early 1980 “type 0” dispensers will work. The version
37000 PIB/Plus board allows full programming capabilities from a third party device
and does not require a 2400 Console to complete the station programming.
•
In the Wayne Data Distribution Box there are switches labeled BYPASS and AUTO.
There may be one switch per dispenser or one switch per side depending on the vintage
of the Wayne devices. Any switches that are not wired to a dispenser must be in the
BYPASS position. If any of the switches that are not wired to a dispenser are in the
AUTO position it will create a break in the communication loop and none of the dis-
pensers will come up on-line.
•
The Wayne dispensers must be addressed starting with number 1, regardless of the
actual pump number that it is configured as in the Site Controller.
•
The baud rate on Wayne controller must set to communicate at 1200 bps with the Site
Controller.
SCII cabling and port jumper configuration
The Wayne 2400 Controller is connected to either port 1 or 3 of the SCII with a C04654 (1:1, 25
pin male to 25 pin female) cable. The cable comes in 8 ft lengths. The maximum distance for this
cable is 100 ft. The pins in the cable are wired like the following: