Pump.bin – Gasboy CFN Site Controller User Manual
Page 50

42
Wayne
Pump Interface Manual v1.3
Gasboy CFN Series
03/20/03
PUMP.BIN
In PUMP.BIN, the Wayne pump types must have options 1, 2, 5, 7, & 9. Option 3 must be
included if the dispensers have the Cash/Credit feature.
Note: The FRAMOS.BIN file on the Release disk must have a date of 01/29/93 or later in order
to work properly with dispenser presets.
For Wayne pumps:
•
The cash price must be lower than or equal to the credit price.
•
The pump limit must be $999 for the cash/credit selection to work.
•
All Wayne dispensers must be configured in sequential, consecutive order. All Wayne
dispensers must be addressed as starting with number 1, regardless of the actual pump
numbers that they are configured with in the Site Controller.
•
In the Wayne Data Distribution Box, any switches that are not wired to a dispenser must
be in the Bypass position.
•
The last digit of the price code determines the grade of fuel as far as the Wayne control-
ler is concerned (6, 16, 26, and 36 are the same product).
•
All price codes for a side of a dispenser must be in the same decade (i.e. you cannot use
price code 3 for hose 1 and price code 12 for hose 2 on the same side of a dispenser.
For non-blenders:
•
each hose must be assigned a price code in ranges 1-5, 11-15, 21-25, 31-35; all hoses on
a pump must be in the same decade.
For all blenders:
•
The blend ratio must be the same for price codes with the same last digit (price codes 6,
16, 26, and 36 must be for the same blend ratio).
•
use price codes 6-9, 16-19, 26-29, 36-39 for blended hoses. Use price codes 4, 14, 24,
34 for low feedstock (non-blended hoses). Use price codes 5, 15, 25, 35 for high feed-
stock (non-blended hoses).
•
product names for products in blended hoses should contain blend rate (for example,
blended 40%, using a percent sign); do not use a percent sign in non-blended hoses.
For fixed blenders:
•
hose 1 is always a non-blended, low-feedstock hose and must have price code 4 (or 14
or 24 or 34). Hose 3 is always a non-blended, high-feedstock hose and must have price
code 5 (or 15 or 25 or 35). Hose 2 is the blended hose and must have a price code in
ranges 6-9, 16-19, 26-29, 36-39. Hose 2 and 4 are fictitious.
For variable 5-product blenders:
•
hoses 1-5 must use price codes 4-9, 14-19, 24-29, 34-39, with no repeats.
For variable 3-product blenders:
•
assign 5 hoses, but assign price code 99 to hoses 2 and 4 since the system uses only
hoses 1, 3, and 5.
•
With SCII version 2.3 and CFN3 version 3.3, for Wayne models V580 and V590U, do
not assign 5 hoses but use Option 23 of the submenu #3 in PUMP.BIN. With this