5 islander ii, Islander ii to tokheim pumps, Cabling and port jumper configuration – Gasboy CFN Site Controller User Manual
Page 43: Islander ii

Pump Interface Manual v1.3
Islander II
35
03/20/03
Gasboy CFN Series
5
Islander II
This chapter describes how to connect Tokheim and Wayne electronic pumps to an Islander. For
setting up the site configuration and dispenser settings, refer to the Tokheim chapter starting on
page 2, or the WAYNE chapter starting on page 40. For DPTs or WAYNE CATS, refer to either
the Tokheim or Wayne chapters.
Islander II to Tokheim Pumps
Cabling and port jumper configuration
The Tokheim Splitter is required to establish an electronic interface between the Islander II and
any Tokheim electronic pumps/remote dispensers. The Tokheim splitter is connected to either
port 1 (TB5) or 3 (TB6) of the Islander II with either a C05756 25 pin D-type connector (female)
or a C07262 Gasboy ISL/TOK termination box. The maximum distance, including all cables,
from the Islander II to the Tokheim 67 interface box is 350 feet. The maximum distance,
including all cables, from the Islander II to the Tokheim 98 interface box is 250 feet. The
C05756 connector can accept up to a maximum of 22 AWG wire. The C07262 termination box
will accept up to 18 AWG wire. All RS-232 requirements defined in the Islander II Installation
Manual C35963 apply.
The SCII CPU K1 (port1) or K2 (port 3) jumper patch must be configured as follows to
communicate with the Tokheim pumps.
The jumpers on the Site Communication I/O board in the head of the Islander (on the inside
of the left partition) for port 1 or port 3 must be configured as shown in the following
illustration:
3
2
1
1
0
2
3
4
5
6
8
9
A
7
K1
3
2
1
1
0
2
3
4
5
6
8
9
A
7
K2