beautypg.com

Trending, Power system stabilizer – Basler Electric DECS-400 User Manual

Page 64

background image

52

9369700990 Rev R

Data recording may be triggered by logic triggers, level triggers, or manually through BESTCOMS.

Logic triggers allow data recording to occur as a result of an internal or external status change of the
DECS-400.

Level triggering allows data record triggering based on the value of one of the internal variables. The
value can be a minimum or maximum value and it can be specified to trigger a record when the monitored
variable crosses a minimum threshold from above, or a maximum threshold from below. A minimum and
maximum threshold may also be selected for the monitored variable, causing the monitored value to
trigger a record when it rises above its maximum or decreases below its minimum.

A standard backup battery maintains real-time clock operation in the event that control power is lost.
Refer to the Maintenance chapter for instructions on replacing the battery.

Trending

The trend log records the activity of parameters over an extended period of time. Up to six parameters
from the following list can be selected for monitoring over a period ranging from one hour to 30 days.

Auxiliary Voltage Input

AVR PID Error Signal Input

Bus Frequency

Bus Voltage

Control Output

Cross Current Input

Field Current

Field Voltage

Frequency Response

Generator Average Current

Generator Average Voltage

Generator Frequency

Generator Ia

Generator Ib

Generator Ic

Generator kVA

Generator kvar

Generator kW

Generator Power Factor

Generator Vab

Generator Vbc

Generator Vca

Negative Sequence Current

Negative Sequence Voltage

Overexcitation Controller Output

PF Mode Output

Phase Angle Ia - Vca

Phase Angle Iaux - Vca

Phase Angle Ib - Vca

Phase Angle Ic - Vca

Phase Angle Vab

Phase Angle Vbc

PID Integrator State

Positive Sequence Current

Positive Sequence Voltage

PSS Electrical Power

PSS Filtered Mechanical Power

PSS Final Output

PSS Lead-Lag #1

PSS Lead-Lag #2

PSS Lead-Lag #3

PSS Lead-Lag #4

PSS Mechanical Power

PSS Mechanical Power LP #1

PSS Mechanical Power LP #2

PSS Mechanical Power LP #3

PSS Mechanical Power LP #4

PSS Post-Limit Output

PSS Power HP #1

PSS Pre-Limit Output

PSS Speed HP #1

PSS Synthesized Speed

PSS Terminal Voltage

PSS Torsional Filter #1

PSS Torsional Filter #2

PSS Washed Out Power

PSS Washed Out Speed

Stator Current Limiter Output

Terminal Frequency Deviation

Time Response

Underexcitation Controller Output

The trend log has a sampling rate of 1,200 data points per record.

Power System Stabilizer

The optional, integrated PSS is an IEEE type PSS2A, dual input, “integral of accelerating power” stabilizer
that provides supplementary damping for low-frequency, local-mode oscillations and power system
oscillations.

Functional Description

DECS-400