Holding registers for metering, group 1 – Basler Electric DECS-400 User Manual
Page 226

214
9369700990 Rev R
Registers
Data Description
Access
Data
Format
40045
2nd character of the boot program version
R
UINT8
40046
3rd character of the boot program version
R
UINT8
40047
4th character of the boot program version
R
UINT8
40048
5th character of the boot program version
R
UINT8
40049
6th character of the boot program version
R
UINT8
40050
7th character of the boot program version
R
UINT8
40051
Last character of the boot program version
R
UINT8
40052
1st character of the boot program date
R
UINT8
40053
2nd character of the boot program date
R
UINT8
40054
3rd character of the boot program date
R
UINT8
40055
4th character of the boot program date
R
UINT8
40056
5th character of the boot program date
R
UINT8
40057
6th character of the boot program date
R
UINT8
40058
7th character of the boot program date
R
UINT8
40059
8th character of the boot program date
R
UINT8
40060
Last character of the boot program date
R
UINT8
40061 to
40200
Reserved for future C1 data
R
Not
Defined
Holding Registers for Metering, Group 1
Table 36. Information Category C2—Metering, Group 1
Registers
Data Description
Access
Data
Format
40201
Leading/lagging load indicator 0 = leading load, 1 = lagging load
R
UINT16
40202
Motoring/generating indicator 0 = motoring, 1 = generating
R
UINT16
40203
Status of front panel LEDs (bit flags where 0 = off and 1 = on)
b0 = null balance, b1 = PSS active, b2 = pre-position, b3 = upper limit,
b4 = lower limit, b5 = edit, b6-b15 = unassigned
R
UINT16
40204
Contact input states: b0 = start, b1 = stop, b2 = auto, b3 = manual, b4 =
raise, b5 = lower, b6 = sw1, b7 = sw2, b8 = sw3, b9 = sw4, b10 = sw5,
b11 = sw6, b12 = sw7, b13 = sw8, b14 = sw9, b15 = sw10
R
UINT16
40205
Voltage matching status indicator
R
UINT16
40206
Adjustment range, in percent, of the active setpoint
R
UINT16
40207
Annunciation status bit flags (0 = clear and 1 = annunciation is present)
b0 = field overvoltage, b1 = field overcurrent, b2 = generator undervoltage,
b3 = generator overvoltage, b4 = underfrequency, b5 = in OEL, b6 = in
UEL, b7 = in FCR mode, b8 = no sensing, b9 = setpoint lower limit, b10 =
setpoint upper limit, b11 = generator failed to build up, b12 = generator
below 10 Hz, b13 = field overtemperature, b14 = EDM open diode, b15 =
EDM shorted diode
R
UINT16
40208
Annunciation status bit flags (0 = clear and 1 = annunciation is present)
b0 = loss of field, b1 = in SCL, b2 = V/Hz, b3 = loss of FIT, b4 = power
low, b5 = PSS V unbalance, b6 = PSS I unbalance, b7 = PSS power
below threshold, b8 = PSS speed failure, b9 = PSS voltage limit, b10 =
clock reset, b11 = loss of IRIG, b12-b15 = unassigned
R
UINT16
40209
Protection status bit flags (0 = clear and 1 = status present)
b0 = field overvoltage, b1 = field overcurrent, b2 = generator undervoltage,
b3 = generator overvoltage, b4 = underfrequency, b5 = in OEL, b6 = in
UEL, b7 = in FCR mode, b8 = no sensing, b9 = setpoint lower limit, b10 =
setpoint upper limit, b11 = generator failed to build up, b12 = generator
below 10 Hz, b13 = field overtemperature, b14 = EDM open diode, b15 =
EDM shorted diode
R
UINT16
40210
Protection status bit flags (0 = clear and 1 = status present)
B0 = loss of field, b1 = in SCL, b2 = V/Hz, b3 = loss of FIT, b4 = power
low, b5 = PSS V unbalance, b6 = PSS I unbalance, b7 = PSS power
below threshold, b8 = PSS speed failure, b9 = PSS voltage limit, b10 =
clock reset, b11 = loss of IRIG, b12-b15 = unassigned
R
UINT16
Modbus™ Communication
DECS-400