Basler Electric DECS-400 User Manual
Page 238

226
9369700990 Rev R
Registers
Data Description
Access
Data
Format
43628
Relay 3 Contact Status
RW
UINT16
43629
Relay 3 Momentary Time
RW
UINT16
43630 to
43675
Reserved for future C11 use
R
Not
Defined
43676
Relay 4 State
RW
UINT16
43677
Relay 4 Contact Type
RW
UINT16
43678
Relay 4 Contact Status
RW
UINT16
43679
Relay 4 Momentary Time
RW
UINT16
43680 to
43725
Reserved for future C11 use
R
Not
Defined
43726
Relay 5 State
RW
UINT16
43727
Relay 5 Contact Type
RW
UINT16
43728
Relay 5 Contact Status
RW
UINT16
43729
Relay 5 Momentary Time
RW
UINT16
43730 to
43775
Reserved for future C11 use
R
Not
Defined
43776
Relay 6 State
RW
UINT16
43777
Relay 6 Contact Type
RW
UINT16
43778
Relay 6 Contact Status
RW
UINT16
43779
Relay 6 Momentary Time
RW
UINT16
43780 to
44125
Reserved for future C11 use
R
Not
Defined
Holding Registers for General ASCII and Modbus Communication Parameters
Table 46. Information Category C12—General ASCII and Modbus Communication Parameters
Registers
Data Description
Access
Data
Format
44126
Baud rate of Front communication port 0, RS-232, Data Range:1200, 2400,
4800, 9600,19200, Default 9600
R
UINT16
44127
Baud rate of Rear communication port 1, RS-485, Data Range:1200, 2400,
4800, 9600,19200, Default 9600
R
UINT16
44128
Baud rate of Rear communication port 2, RS-485, Data Range:4800,
9600,19200, Default 9600
RW
UINT16
44129
Modbus port Parity, valid only for Rear RS-485 port. ‘O’ = 79= 0x4F for Odd
Parity, ‘E’ = 69= 0x45 or Even Parity, and ‘N’ =78= 0x4E for None
RW
UINT8
44130
Modbus port Stop Bits, 1 for 1 Stop Bit, 2 for 2 Stop bits, Default value: 2
RW
UINT8
44131
DECS400 Polling Address, valid only for Rear RS-485 port. 0 for
Broadcast address, 1 to 247 for slave address, Default: 247
RW
UINT16
44132
Modbus Response Delay Time Parameter in ms (Default value: 10ms) Data
Range 0-200, step size 10
RW
UINT16
44133
System Clock Month
RW
UINT16
44134
System Clock Day
RW
UINT16
44135
System Clock Year
RW
UINT16
44136
System Clock Daylight Savings Time, 0 = Daylight Savings Time On, 1 =
Daylight Savings Time Off
RW
UINT16
44137
System Clock Hour
RW
UINT16
44138
System Clock Minute
RW
UINT16
44139
System Clock Second
RW
UINT16
44140
System Clock Time Format, 0 = 12 hour format, 1 = 24 hour format.
RW
UINT16
44141
System Clock AM/PM. 'A' = 65 = 0x41 for AM, 'P' = 80 = 0x50 for PM, 'X' =
58 = 0x3A for none
RW
UINT16
44142 to
44200
Reserved for future C12 use
R
Not
Defined
Modbus™ Communication
DECS-400