Basler Electric DECS-400 User Manual
Page 211
![background image](https://www.manualsdir.com/files/773927/content/doc211.png)
9369700990 Rev R
199
Manual
Puts the DECS-400 in manual mode (latching).
Pre Position 1
Returns the active setpoint to its programmed pre position 1 level.
Raise
Raises the active setpoint (momentary).
Lower
Lowers the active setpoint (momentary).
PF Var
52J/K contact (forces the regulator in PF/var mode when it is true) (dependent upon BESTCOMS
selection).
Dual PID Selection
Activates the secondary gains (non-latching) (secondary gains are only active when the output is active).
Alarm Reset
A momentary input resets all DECS-400 alarms.
Secondary DECS
Activates the tracking mode of the DECS-400 (non-latching).
Var PF Selection
0=Droop, 1=Droop/var/PF selection available through BESTCOMS.
Droop Enabled
Acts as a permissive for the checkbox in BESTCOMS (if this output is included in the logic, or it has been
in the logic since the last time power was cycled, it must be set true before the regulator will enter droop
mode).
Line Drop
Controls line drop compensation in the same way as the Droop Enabled output.
Cross Current Compensation
Controls CCC in the same way as the Droop Enabled output.
Internal Tracking
Acts as a permissive to the BESTCOMS enable switch, but the BESTCOMS switch is not a permissive to
this output (if this output is included in the logic, or it has been in the logic since the last time power was
cycled, it must be set true before the regulator will enter this mode).
External Tracking
Controls external tracking in the same way as the Internal Tracking output.
Voltage Matching
When this is set true, voltage matching is enabled (disabled when on-line).
Below 10 Hz
Below 10 Hz alarm.
DECS-400
Programmable Logic