exclusive-ORed with the fixed polynomial value A001 (hex) prior to the next shift. Once all bytes of the
message have undergone the above algorithm, the CRC register will contain the message CRC value to
be placed in the error check field.
DECS-400 Modbus
™ Register Space
Modbus address space from 40000 to 49999 refers to function codes 3, 6, and 16. The DECS-400 uses
address space from 40001 to 44999 (4,999 registers). This address space is divided into 14 areas,
referred to as information categories.
Table 34 provides a statistical summary for each information category.
Table 34. Information Category Summary
Information
Category ID
Information
Category
Total # of
Reserved
Holding
Registers
Holding
Register
Address
Space
Number
of Used
Registers
Access
Privilege
Data Types
Mapped to
Registers
(Total # of
Variables)
C1
Version Data
200
40001 to
40200
60
R
UINT8
C2
Metering,
Group 1
199
40201 to
40399
61
R
UINT16: 11
FLOAT: 50
C3
System
Configuration
199
40401 to
40599
40
RW: 39
R: 1
UINT16: 11
FLOAT: 29
C4
Operating
Mode
Parameters
97
40604 to
40700
45
RW: 23
R: 22
UINT: 45
C5
Setpoint
Parameters
449
40701 to
41149
58
RW: 34
R: 24
UINT16: 8
FLOAT: 50
C6
Startup
Parameters
199
41151 to
41349
17
RW: 16
R: 1
FLOAT: 16
UINT16: 1
C7
Limiter
Parameters
1,124
41351 to
42474
68
RW: 65
R: 3
FLOAT: 62
UINT16: 6
C8
Gain Registers
524
42476 to
42999
33
RW: 32
R: 1
UINT16: 1
FLOAT: 32
C9
Protection
Function
Parameters
127
43001 to
43127
29
RW: 23
R: 6
UINT16: 13
FLOAT: 16
C10
Exciter Diode
Monitor
Parameters
149
43376 to
43492
26
RW
UINT16: 8
FLOAT: 18
C11
Relay
Parameters
600
43526 to
44125
24
RW
UINT16
C12
ASCII and
Modbus
Communication
Parameters
125
44126 to
44250
16
RW: 14
R: 2
UINT8: 2
UINT14: 6
C13
Metering,
Group 2
50
44201 to
44250
3
RW
UINT16
C14
PSS
Parameters
749
44251 to
44999
91
RW: 89
R: 2
UINT16: 23
FLOAT: 68
Modbus™ Communication