Holding registers for setpoint parameters – Basler Electric DECS-400 User Manual
Page 230
![background image](https://www.manualsdir.com/files/773927/content/doc230.png)
218
9369700990 Rev R
Registers
Data Description
Access
Data
Format
40726
Enables traverse rate to the pre-position 1 for the mode
RW
UINT16
40727
Enables traverse rate to the pre-position 2 for the mode
RW
UINT16
40728
Enables traverse rate to the pre-position 1 for the mode
RW
UINT16
40730 to
40899
Reserved for future C4 use
R
Not
Defined
40900
Traverse time, in seconds, between mode’s min and max settings
RW
FLOAT
40902
Traverse time, in seconds, between mode’s min and max settings
RW
FLOAT
40904
Traverse time, in seconds, between mode’s min and max settings
RW
FLOAT
40906
Traverse time, in seconds, between mode’s min and max settings
RW
FLOAT
40908
Traverse time, in seconds, between mode’s min and max settings
RW
FLOAT
40910
Traverse time, in seconds, between mode’s min and max settings
RW
FLOAT
40912
Traverse time, in seconds, between mode’s min and max settings
RW
FLOAT
40914
Traverse time, in seconds, between mode’s min and max settings
RW
FLOAT
40916
Traverse time, in seconds, between mode’s min and max settings
RW
FLOAT
40918
Traverse time, in seconds, between mode’s min and max settings
RW
FLOAT
Holding Registers for Setpoint Parameters
Table 39. Information Category C5—Setpoint Parameters
Registers
Data Description
Access
Data
Format
40701
FCR pre-position 1 mode: 0=maintained, 1=release
RW
UINT16
40702
AVR pre-position 1 mode: 0=maintained, 1=release
RW
UINT16
40703
VAR pre-position 1 mode: 0=maintained, 1=release
RW
UINT16
40704
PF pre-position 1 mode: 0=maintained, 1=release
RW
UINT16
40705
FCR pre-position 2 mode: 0=maintained, 1=release
RW
UINT16
40706
AVR pre-position 2 mode: 0=maintained, 1=release
RW
UINT16
40707
VAR pre-position 2 mode: 0=maintained, 1=release
RW
UINT16
40708
PF pre-position 2 mode: 0=maintained, 1=release
RW
UINT16
40709
FVR pre-position 1 mode: 0=maintained, 1=release
RW
UINT16
40710
FVR pre-position 2 mode: 0=maintained, 1=release
RW
UINT16
40751
FCR (Field Current Regulator) mode setpoint in amps; adjustment range is
determined by registers (40761-62) and (40769-70)
RW
FLOAT
40753
AVR (Automatic Voltage Regulator) mode setpoint in volts; adjustment
range is determined by registers(40763-64) and (40771-72)
RW
FLOAT
40755
VAR mode setpoint in kvars; adjustment range is determined by registers
(40765-66) and (40773-74)
RW
FLOAT
40757
PF mode setpoint; adjustment range is determined by registers (40767-68)
and (40775-76)
RW
FLOAT
40759
Reactive Droop setting in % of rated generator voltage; adjustable from -30
to +30% in .1% increments
RW
FLOAT
40761
FCR minimum setpoint (in amps) = % of nominal x rated field current:(regs.
40801-02) x (regs. 40479-80) / 100
R
FLOAT
40763
AVR minimum setpoint (in volts) = % of nominal x rated generator
voltage:(regs. 40803-04) x (regs. 40473-74) / 100
R
FLOAT
40765
VAR minimum setpoint (in kvars) = % of nominal x rated generator
VA:(regs. 40805-06) x rated VA / 100
R
FLOAT
40767
PF maximum setpoint = registers 40807-08
R
FLOAT
40769
FCR maximum setpoint (in amps) = % of nominal x rated field current:(regs.
40809-10) x (regs. 40479-80) / 100
R
FLOAT
40771
AVR maximum setpoint (in volts) = % of nominal x rated generator
voltage:(regs. 40811-12) x (regs. 40473-74) / 100
R
FLOAT
40773
VAR maximum setpoint (in kvars) = % of nominal x rated generator
VA:(regs. 40813-14) x rated VA / 100
R
FLOAT
40775
PF minimum setpoint = registers 40815-16
R
FLOAT
40777
FCR mode traverse rate, adjustable from 10 to 200 seconds in 1 second
increments
RW
FLOAT
Modbus™ Communication
DECS-400