Specifications
DECS-400 electrical and physical specifications are listed in the following paragraphs.
Operating Power
AC Input (Style XCXX Only)
Nominal ......................................... 120 Vac
Range ............................................ 82 to 132 Vac
Frequency ..................................... 50/60 Hz
Burden ........................................... 50 VA
Terminals....................................... C2 (N), C3 (L)
DC Input (Style XCXX, XLXX)
Nominal
Style XCXX ............................. 125 Vdc
Style XLXX .............................. 24/48 Vdc
Range
Style XCXX
90 to 150 Vdc
Style XLXX
16 to 60 Vdc
Burden ........................................... 30 W
Terminals....................................... C4 (BATT–), C5 (BATT+)
Generator Voltage Sensing
Configuration ................................. 1-phase (A-phase (E1) to C-phase (E3)) or 3-phase
Ranges .......................................... 120 V or 240 V, automatically selected
Burden ........................................... <1 VA
Terminals....................................... A9, (E1), A10 (E2), A11 (E3)
50 Hertz Sensing
Range 1 ......................................... 85 to 127 Vac
Range 2 ......................................... 170 to 254 Vac
60 Hertz Sensing
Range 1 ......................................... 94 to 153 Vac
Range 2 ......................................... 187 to 305 Vac
Bus Voltage Sensing
Configuration ................................. 1-phase (A-phase (BUS1) to C-phase (BUS3))
Ranges .......................................... 120 V or 240 V, automatically selected
Burden ........................................... <1 VA
Terminals....................................... A13 (BUS1), A14 (BUS3)
50 Hertz Sensing
Range 1 ......................................... 85 to 127 Vac
Range 2 ......................................... 170 to 254 Vac
60 Hertz Sensing
Range 1 ......................................... 94 to 153 Vac
Range 2 ......................................... 187 to 305 Vac