Programmable inputs, Terminals, Accessory input (remote setpoint control) – Basler Electric DECS-400 User Manual
Page 171: Voltage input, Current input, Control outputs, Voltage control output

9369700990 Rev R
159
Programmable Inputs
Any of the 10 programmable inputs can be configured, through the integrated programmable logic, with
the following functions.
•
2
nd
PID Settings Selection
•
2
nd
Pre-Position
•
Phase Rotation
•
Pre-Position
•
PSS Enable
•
PSS Motor/Generator Mode
•
PSS Parameters Set Selection
•
Reactive Differential Compensation Enable
•
Reactive Droop Compensation Enable
•
Secondary Enable
•
Speed Switch Enable
•
Unit/Parallel Operation (52 L/M)
•
Var/Power Factor Enable (52 J/K)
Terminals
Start ............................................... B1 (START), B2 (COM)
Stop ............................................... B3 (STOP), B2 (COM)
AVR ............................................... B4 (AVR), B5 (COM)
Manual ........................................... B6 (Man), B5 (COM)
Raise ............................................. B7 (RAISE), B8 (COM)
Lower ............................................. B9 (LOWER), B8 (COM)
Programmable 1 ............................ B10 (SW1), B11 (COM)
Programmable 2 ............................ B12 (SW2), B11 (COM)
Programmable 3 ............................ C23 (SW3), C24 (COM)
Programmable 4 ............................ C25 (SW4), C24 (COM)
Programmable 5 ............................ C26 (SW5), C27 (COM)
Programmable 6 ............................ C28 (SW6), C27 (COM)
Programmable 7 ............................ C29 (SW7), C30 (COM)
Programmable 8 ............................ C31 (SW8), C30 (COM)
Programmable 9 ............................ C32 (SW9), C33 (COM)
Programmable 10 .......................... C34 (SW10), C33 (COM)
Accessory Input (Remote Setpoint Control)
Voltage Input
Range ............................................ –10 Vdc to +10 Vdc
Terminals....................................... A16 (V+), A17 (V–)
Current Input
Range ............................................ 4 mAdc to 20 mAdc
Terminals....................................... A19 (I+), A20 (I–)
Control Outputs
The excitation setpoint is controlled by either an analog voltage output or analog current output.
Voltage Control Output
Range ............................................
±10 Vdc or 0 to +10 Vdc
Terminals....................................... D14 (VC+), D15 (RTNC)
DECS-400
Specifications