Figure 74. Data Log Screen, Mode Triggers Tab
Limiter Mode. This setting enables a data log report to be triggered when the underexcitation limiter,
overexcitation limiter, or stator current limiter are active. Additionally, a data log report can be triggered
when two of the limiters are active. The available limiter mode selections are listed below:
•
UEL (underexcitation limiter)
•
OEL (overexcitation limiter)
•
UEL & OEL
•
SCL (stator current limiter)
•
UEL & SCL
•
OEL & SCL
•
UEL, OEL & SCL
•
VARL (reactive power limiter)
•
VARL & UEL
•
VARL & OEL
•
VARL, OEL, & UEL
•
VARL & SCL
•
VARL, SCL, & UEL
•
VARL, SCL, & OEL
•
VARL, SCL, OEL, & UEL
•
Off (no limiters active)
•
NO TRIGGER (disables a limiter mode
trigger)
Voltage Matching Mode. This setting enables a data log report to be triggered when Voltage Matching
mode is off or on. Selecting NO TRIGGER disables a Voltage Matching mode trigger.
Secondary DECS Mode. This setting enables a data log report to be triggered when the DECS-400 is
functioning as the primary DECS-400 or secondary DECS-400 in a redundant DECS-400 system.
Selecting NO TRIGGER disables a Secondary DECS Mode trigger.
PSS Controller Mode. This setting enables a data log report to be triggered when the PSS function is
enabled or disabled. Selecting NO TRIGGER disables a PSS Controller mode trigger.
Manual Mode. This setting enables a data log report to be triggered when a transfer to Manual (either
FCR or FVR) mode occurs.
Droop Mode. This setting enables a data log report to be triggered when Droop mode is enabled or
disabled. Selecting NO TRIGGER disables a Droop mode trigger.
Line Drop Mode. This setting enables a data log report to be triggered when Line Drop mode is enabled
or disabled. Selecting NO TRIGGER disables a Line Drop mode trigger.