Table 12 – Basler Electric DECS-400 User Manual
Page 141

9369700990 Rev R
129
Table 12. Contact Input Terminals
Terminal
Description
B1 (START)
∗ Positive terminal of Start contact input
B2 (COM)
Common terminal of Start and Stop contact inputs
B3 (STOP)
∗
Positive terminal of Stop contact input
B4 (AVR)
∗
Positive terminal of AVR contact input
B5 (COM)
Common terminal of AVR and FCR contact inputs
B6 (MAN)
∗
Positive terminal of Manual contact input
B7 (RAISE) †
Positive terminal of Raise contact input
B8 (COM)
Common terminal of Raise and Lower contact inputs
B9 (LOWER) † Positive terminal of Lower contact input
B10 (SW1)
Positive terminal of programmable contact input #1
B11 (COM)
Common terminal of programmable contact inputs #1 and #2
B12 (SW2)
Positive terminal of programmable contact input #2
C23 (SW3)
Positive terminal of programmable contact input #3
C24 (COM)
Common terminal of programmable contact inputs #3 and #4
C25 (SW4)
Positive terminal of programmable contact input #4
C26 (SW5)
Positive terminal of programmable contact input #5
C27 (COM)
Common terminal of programmable contact inputs #5 and #6
C28 (SW6)
Positive terminal of programmable contact input #6
C29 (SW7)
Positive terminal of programmable contact input #7
C30 (COM)
Common terminal of programmable contact inputs #7 and #8
C31 (SW8)
Positive terminal of programmable contact input #8
C32 (SW9)
Positive terminal of programmable contact input #9
C33 (COM)
Common terminal of programmable contact inputs #9 and #10
C34 (SW10)
Positive terminal of programmable contact input #10
∗ Functions are activated by a momentary input.
† Functions are active only when the corresponding contact input is active.
Field Voltage and Current
Field voltage and current signals are supplied to connector P1 of the DECS-400 by the Field Isolation
Module. A cable, supplied with the Field Isolation Module, connects from Field Isolation Module connector
J1 to DECS-400 connector P1.
IRIG
The clock function of the DECS-400 is synchronized with a time code source through the application of a
standard IRIG-B signal to the IRIG terminals. Refer to the Specifications chapter for specifications
pertaining to the IRIG input. Table 13 lists the IRIG terminals.
Table 13. IRIG Terminals
Terminal
Description
D1 (IRIG+)
Positive IRIG terminal
D2 (IRIG–)
Negative IRIG terminal
DECS-400
Installation