140
9369700990 Rev R
Figure 100. BESTCOMS Metering Screen, Operation Tab
•
Verify that field flashing and shutdown occurs with the start and stop functions. ................. ________
•
If field flashing is used, verify alarms for failure to build voltage. .......................................... ________
•
Verify alarm annunciation at front panel HMI, in BESTCOMS, and remote indicators. ........ ________
•
With excitation off, check AVR/FCR transfer using the front panel HMI, remote
switches, and BESTCOMS. ................................................................................................... ________
•
Verify transfer indications from the front panel HMI, BESTCOMS, and any remote
indicators. .............................................................................................................................. ________
Note
For station power systems, field flashing is not used. When the system
is energized with the field connected, the field current will build to the
value specified on the FCR setting screen. During the test, the
suggested setting for the no-load field current is 20% and the FCR Kg
gain is 1,000. Verify that the system is stable.
•
Check for proper raise/lower limits. ....................................................................................... ________
•
Verify raise/lower indications at the front panel HMI, through BESTCOMS, and from
remote indicators. .................................................................................................................. ________
Control Gain Settings
Establish the gain settings for the active settings group.
Commissioning
DECS-400