Basler Electric DECS-400 User Manual
Page 231

9369700990 Rev R
219
Registers
Data Description
Access
Data
Format
40779
AVR mode traverse rate, adjustable from 10 to 200 seconds in 1 second
increments
RW
FLOAT
40781
VAR mode traverse rate, adjustable from 10 to 200 seconds in 1 second
increments
RW
FLOAT
40783
PF mode traverse rate, adjustable from 10 to 200 seconds in 1 second
increments
RW
FLOAT
40785
FCR mode setpoint pre-position 1; adjustment range is determined by
registers (40761-62) and (40769-70)
RW
FLOAT
40787
AVR mode setpoint pre-position 1; adjustment range is determined by
registers (40763-64) and (40771-72)
RW
FLOAT
40789
VAR mode setpoint pre-position 1; adjustment range is determined by
registers (40765-66) and (40773-74)
RW
FLOAT
40791
PF mode setpoint pre-position 1; adjustment range is determined by
registers (40767-68) and (40775-76)
RW
FLOAT
40793
FCR mode setpoint step size = setpoint range / (traverse rate x 10):[(regs.
40769-70) - (regs. 40761-62)] / [(regs. 40777-78) x 10]
R
FLOAT
40795
AVR mode setpoint step size = setpoint range / (traverse rate x 20):[(regs.
40771-72) - (regs. 40763-64)] / [(regs. 40779-80) x 20]
R
FLOAT
40797
VAR mode setpoint step size = setpoint range / (traverse rate x 20):[(regs.
40773-74) - (regs. 40765-66)] / [(regs. 40781-82) x 20]
R
FLOAT
40799
PF mode setpoint step size = setpoint range / (traverse rate x 20):[2 +
(regs. 40775-76) - (regs. 40767-68)] / [(regs. 40783-84) x 20]
R
FLOAT
40801
FCR mode setpoint's minimum (in % of rated field current), adjustable from
0 to 100%, in .1% increments
RW
FLOAT
40803
AVR mode setpoint's minimum (in % of rated generator output voltage),
adjustable from 70 to 100%, in .1% increments
RW
FLOAT
40805
VAR mode setpoint's minimum (in % of rated generator VA), adjustable
from -100 to +100%, in .1% increments
RW
FLOAT
40807
PF mode setpoint maximum, adjustable from 0.5 to 1.0, in .005 increments
RW
FLOAT
40809
FCR mode setpoint's maximum (in % of rated field current), adjustable from
100 to 120%, in .1% increments
RW
FLOAT
40811
AVR mode setpoint's maximum (in % of rated generator output voltage),
adjustable from 100 to 110%, in .1% increments
RW
FLOAT
40813
VAR mode setpoint's maximum (in % of rated generator VA), adjustable
from -100 to +100%, in .1% increments
RW
FLOAT
40815
PF mode setpoint minimum, adjustable from -1.0 to -0.5, in .005 increments
RW
FLOAT
40817
Minimum value for FCR mode setpoint's adjustable minimum (in % of rated
field current) = 0%
R
FLOAT
40819
Minimum value for AVR mode setpoint's adjustable minimum (in % of rated
generator ouput voltage) = 70%
R
FLOAT
40821
Minimum value for VAR mode setpoint's adjustable minimum (in % of rated
generator VA) = -100%
R
FLOAT
40823
Maximum value for PF mode setpoint's adjustable minimum
R
FLOAT
40825
Maximum value for FCR mode setpoint's adjustable maximum (in % of
rated field current) = 120%
R
FLOAT
40827
Maximum value for AVR mode setpoint's adjustable maximum (in % of
rated generator ouput voltage) = 110%
R
FLOAT
40829
Maximum value for VAR mode setpoint's adjustable maximum (in % of
rated generator VA) = 100%
R
FLOAT
40831
Minimum value for PF mode setpoint's adjustable maximum
R
FLOAT
40833
Step size for FCR mode setpoint's adjustable maximum (in % of rated field
current) = 0.1%
R
FLOAT
40835
Step size for AVR mode setpoint's adjustable maximum (in % of rated
generator output voltage) = 0.1%
R
FLOAT
40837
Step size for VAR mode setpoint's adjustable maximum (in % of rated
generator VA) = 0.1%
R
FLOAT
DECS-400
Modbus™ Communication