Holding registers for gain parameters – Basler Electric DECS-400 User Manual
Page 235

9369700990 Rev R
223
Registers
Data Description
Access
Data
Format
41855
Var limiter initial delay for secondary selection
RW
FLOAT
41856 to
42474
Reserved for future C7 use
R
Not
Defined
Note
Effective with firmware version 1.07, AVR and FCR have individual
gain settings. AVR gain settings are read/write with registers 42503
through 42507. FCR gain settings are read/write with registers 42553
through 42559. In versions prior to 1.07, gain settings for both AVR
and FCR are read/write with registers 42503, 42505, and 42507.
Holding Registers for Gain Parameters
Table 42. Information Category C8—Gain Parameters
Registers
Data Description
Access
Data
Format
42476
Active AVR/FCR Gain Setting Group
R
UINT16
42477 to
42500
Reserved for future C8 use
R
Not
Defined
42501
Primary Stability Range (Gain Table Index)
RW
FLOAT
42503
Primary AVR - Proportional Gain Kp
RW
FLOAT
42505
Primary AVR - Integral Gain Ki
RW
FLOAT
42507
Primary AVR - Derivative Gain Kd
RW
FLOAT
42509
OEL - Proportional Gain Kp
RW
FLOAT
42511
OEL - Integral Gain Ki
RW
FLOAT
42513
PF - Integral Gain Ki
RW
FLOAT
42515
VAR - Integral Gain Ki
RW
FLOAT
42517
FCR - Loop Gain Kg
RW
FLOAT
42519
Primary AVR - Loop Gain Kg
RW
FLOAT
42521
VAR - Loop Gain Kg
RW
FLOAT
42523
PF - Loop Gain Kg
RW
FLOAT
42525
OEL - Loop Gain Kg
RW
FLOAT
42527
UEL - Loop Gain Kg
RW
FLOAT
42529
Voltage Matching - Loop Gain Kg
RW
FLOAT
42531
Voltage Matching - Proportional Gain Kp
RW
FLOAT
42533
Voltage Matching - Integral Gain Ki
RW
FLOAT
42541
UEL - Proportional Gain Kp
RW
FLOAT
42543
UEL - Integral Gain Ki
RW
FLOAT
42545
Primary AVR - Derivative Time Constant Td
RW
FLOAT
42547
SCL - Loop Gain Kg
RW
FLOAT
42549
SCL - Proportional Gain Kp
RW
FLOAT
42551
SCL - Integral Gain Ki
RW
FLOAT
42553
FCR - Proportional Gain Kp
RW
FLOAT
42555
FCR - Integral Gain Ki
RW
FLOAT
42557
FCR - Derivative Gain Kd
RW
FLOAT
42559
Primary FCR - Derivative Time Constant Td
RW
FLOAT
42561
FVR Proportional Gain Kp
RW
FLOAT
42563
FVR Integral Gain Ki
RW
FLOAT
42565
FVR Derivative Gain Kd
RW
FLOAT
42567
FVR Derivative Time Constant Td Gain
RW
FLOAT
42569
FVR Loop Gain Kg
RW
FLOAT
42570 to
Reserved for future C8 use
R
Not
DECS-400
Modbus™ Communication