Data Logging
The data logging function of the DECS-400 can record up to six oscillography records. DECS-400
oscillography records use the IEEE Standard Common Format for Transient Data Exchange
(COMTRADE). Each record is time- and date-stamped. After six records have been recorded, the DECS-
400 begins recording the next record over the oldest record. Because all oscillography records are stored
in volatile memory, all records are lost if DECS-400 operating power is interrupted.
Each oscillography record can consist of up to six user-selectable variables with up to 600 data points
recorded for each variable. The interval between records is adjustable from 4 milliseconds to 10 seconds.
Data points may be selected for pre-trigger operation in order to capture events prior to a fault. Up to 599
pre-trigger data points may be selected. Data points not designated for pre-trigger recording are assigned
to the post-trigger portion of the fault record. This feature, combined with the adjustable sample rate,
allows for flexible data sampling around the fault.
A maximum of six variables may be selected to trigger a sequence of events record. The available
variables are listed below.
•
Auxiliary Voltage Input
•
AVR PID Error Signal Input
•
Bus Frequency
•
Bus Voltage
•
Compensated Frequency Deviation
•
Control Output
•
Cross Current Input
•
Field Current
•
Field Voltage
•
Frequency Response
•
Generator Average Current
•
Generator Average Voltage
•
Generator Frequency
•
Generator Ia
•
Generator Ib
•
Generator Ic
•
Generator kVA
•
Generator kvar
•
Generator kW
•
Generator Power Factor
•
Generator Vab
•
Generator Vbc
•
Generator Vca
•
Negative Sequence Current
•
Negative Sequence Voltage
•
Overexcitation Controller Output
•
PF Mode Output
•
Phase Angle Ia - Vca
•
Phase Angle Iaux - Vca
•
Phase Angle Ib - Vca
•
Phase Angle Ic - Vca
•
Phase Angle Vab
•
Phase Angle Vbc
•
PID Integrator State
•
Positive Sequence Current
•
Positive Sequence Voltage
•
PSS Electrical Power
•
PSS Filtered Mechanical Power
•
PSS Final Output
•
PSS Lead-Lag #1
•
PSS Lead-Lag #2
•
PSS Lead-Lag #3
•
PSS Lead-Lag #4
•
PSS Mechanical Power
•
PSS Mechanical Power LP #1
•
PSS Mechanical Power LP #2
•
PSS Mechanical Power LP #3
•
PSS Mechanical Power LP #4
•
PSS Post-Limit Output
•
PSS Power HP #1
•
PSS Pre-Limit Output
•
PSS Speed HP #1
•
PSS Synthesized Speed
•
PSS Terminal Voltage
•
PSS Torsional Filter #1
•
PSS Torsional Filter #2
•
PSS Washed Out Power
•
PSS Washed Out Speed
•
Stator Current Limiter Output
•
Terminal Frequency Deviation
•
Time Response
•
Underexcitation Controller Output
DECS-400
Functional Description