Secondary Protect
Activates secondary protection settings only when it is active (non-latching).
Field Over Voltage
0=Disabled, 1=Enabled (default=1) (Also must be enabled on the Protection screen in BESTCOMS).
Field Over Current
0=Disabled, 1=Enabled (default=1) (Also must be enabled on the Protection screen in BESTCOMS).
Gen Over Voltage
0=Disabled, 1=Enabled (default=1) (Also must be enabled on the Protection screen in BESTCOMS).
Gen Under Voltage
0=Disabled, 1=Enabled (default=1) (Also must be enabled on the Protection screen in BESTCOMS).
Field Over Temp
0=Disabled, 1=Enabled (default=1) (Also must be enabled on the Protection screen in BESTCOMS).
Loss of Field
0=Disabled, 1=Enabled (default=1) (Also must be enabled on the Protection screen in BESTCOMS).
Loss of Sensing
0=Disabled, 1=Enabled (default=1) (Also must be enabled on the Protection screen in BESTCOMS).
Volts per Hz
0=Disabled, 1=Enabled (default=1) (Also must be enabled on the Protection screen in BESTCOMS).
EDM Open
0=Disabled, 1=Enabled (default=1) (Also must be enabled on the Protection screen in BESTCOMS).
EDM Short
0=Disabled, 1=Enabled (default=1) (Also must be enabled on the Protection screen in BESTCOMS).
Loss of Sensing Transfer to Manual
0=Off, 1=On
OEL
0=Disabled, 1=Enabled (default=1) (Also must be enabled on the Limiters screen in BESTCOMS).
UEL
0=Disabled, 1=Enabled (default=1) (Also must be enabled on the Limiters screen in BESTCOMS).
SCL
0=Disabled, 1=Enabled (default=1) (Also must be enabled on the Limiters screen in BESTCOMS).
Secondary OEL
Activates secondary overexcitation limiter settings only when it is active (non-latching).
Secondary UEL
Activates secondary underexcitation settings only when it is active (non-latching).
Secondary SCL
Activates secondary stator current limiter settings only when it is active (non-latching).
Secondary Soft Start
Activates secondary soft start settings only when it is active (non-latching).
Programmable Logic
DECS-400