Basler Electric DECS-400 User Manual
Page 213
![background image](https://www.manualsdir.com/files/773927/content/doc213.png)
9369700990 Rev R
201
OEL Style
0=Summing Point, 1=Takeover (default=1)
OEL Off-Line/On-Line Option
Activates on-line overexcitation limiter settings only when it is active (non-latching).
UEL Style
0=Summing Point, 1=Takeover (default=1)
Secondary PSS
Activates the secondary power system stabilizer settings only when it is active (non-latching).
PSS Control Out
Power system stabilizer control enable.
PSS Test Out
Power system stabilizer test output enable.
PSS Motor Control
Power system stabilizer motor selection.
PSS Seq Control
Power system stabilizer phase rotation.
Modbus Write
RS-485 communication enable.
Modem Write
Modem access enable.
OEL Enabled in Manual Mode
Enables overexcitation limiter when the manual regulator is active.
UEL Enabled in Manual Mode
Enables underexcitation limiter when the manual regulator is active.
Manual FCR Only
Field voltage regulation mode disabled when true.
Inner Loop Enable
0 = disabled, 1 = enabled (default is 0)
Pre-Position Traverse Enable
0 = disabled, 1 = enabled (default is 0)
PSS ROC Enabled
0 = disabled, 1 = enabled (default is 0)
Secondary VARL
Activates the secondary reactive power limiter settings only when this output is active (non-latching).
VARL
0 = disabled, 1 = enabled (default is 0) This output must be enabled on the BESTCOMS Limiters screen.
DECS-400
Programmable Logic