Basler Electric DECS-400 User Manual
Page 106

94
9369700990 Rev R
Figure 62. PSS Screen, Configure Tab
The Rate of Change settings are illustrated in Figure 63 and described in the following paragraphs.
Figure 63. PSS Screen, Rate of Change Tab
Block Time. Once the PSS output is driven to zero during a rate of frequency-change event, it is ramped
back up to its previous, nominal value over the time defined by the Block Time setting. A setting of 0 to 20
seconds may be entered in 0.1 second increments.
Low-Pass Filter Time Constant. This setting can be used to tailor the response of the PSS rate-of-change
function to the application. A setting of 0 to 20 seconds may be entered in 0.01 second increments.
BESTCOMS™ Software
DECS-400
See also other documents in the category Basler Electric Accessories for electrical:
- SMC-250 (6 pages)
- AVC63-2 (2 pages)
- AVC63-2.5 (2 pages)
- AVC63-4D (6 pages)
- AVC63-7 (4 pages)
- AVC63-7F (4 pages)
- AVC Sensing Module (2 pages)
- AVC125-10 (10 pages)
- AVC125-10 (14 pages)
- APR63-5 (6 pages)
- APR63-5X (4 pages)
- BE350 (4 pages)
- VR63-4/UL (2 pages)
- VR63-4A/UL (4 pages)
- VR63-4B (2 pages)
- VR63-4C/UL (2 pages)
- BE300PM (4 pages)
- DECS-100 (86 pages)
- DECS-250N Terminals and Connectors (370 pages)
- DECS-250 Mounting (4 pages)
- DECS-250N Mounting (4 pages)
- MVC232 (4 pages)
- MVC112 (8 pages)
- MVC236 (24 pages)
- BE2000E (82 pages)
- MVC300 (16 pages)
- CBS 212A (28 pages)
- MVC301 (16 pages)
- ICRM-15 (4 pages)
- DGC-2020 Troubleshooting (620 pages)
- DGC-2020ES (252 pages)
- DGC-2020HD (404 pages)
- DGC-2020ES Mounting (2 pages)
- DGC-2020HD Modbus Protocol (318 pages)
- RDP-110 (26 pages)
- BE1-25A (90 pages)
- IDP-800 (70 pages)
- ESD201 (4 pages)
- ESD202 (2 pages)
- IDP-1200 (90 pages)