Alarms Message
The alarms message line remains blank during normal operating conditions. If an enunciable condition
occurs, “ALARMS (PRESS < OR >)” is displayed. Information about the condition is obtained by viewing
the alarm message screen.
Alarm Message Screen
Pressing either the left or right scrolling pushbuttons, while viewing the metering screen, displays the
alarm message screen. This screen displays up to six messages identifying the conditions that led to the
most recent annunciations.
lists the annunciations that may appear on the alarm message screen. When more than one message is
listed, the newest messages are added to the bottom of the list. Once the list contains six messages, any
further annunciations will cause the oldest message to be deleted from the top of the list.
Table 5. Alarm Messages
Annunciation Message
Duration of Message
CLOCK RESET
Maintained until reset
CURRENT UNBALANCE
Automatically reset
EXCESSIVE V/HZ
Maintained until reset
EXCITER DIODE OPEN
Maintained until reset
EXCITER DIODE SHORT
Maintained until reset
FAILED TO BUILD UP
Maintained until reset
FIELD OVER TEMP
Maintained until reset
FIELD OVERCURRENT
Maintained until reset
FIELD OVERVOLTAGE
Maintained until reset
GEN. OVERVOLTAGE
Maintained until reset
GEN. UNDERVOLTAGE
Maintained until reset
LOSS ISOLATION MODULE
Automatically reset
LOSS OF FIELD
Maintained until reset
LOSS OF IRIG
Automatically reset
LOST VOLTAGE SENSING
Maintained until reset
OVEREXCITATION LIMIT
Clears 2 s after end of event
POWER BELOW THRESHOLD
Automatically reset
POWER SUPPLY LOW
Automatically reset
PSS BLOCK
Automatically reset
SPEED FAILURE
Automatically reset
STATOR CURRENT LIMIT
Clears 2 s after end of event
SYSTEM BELOW 10 HZ
Clears 2 s after end of event
UNDEREXCITATION LIMIT
Clears 2 s after end of event
UNDERFREQUENCY
Clears 2 s after end of event
VAR LIMIT
Automatically reset
VOLTAGE LIMIT
Automatically reset
VOLTAGE UNBALANCE
Automatically reset
The list of alarm messages can be cleared by pressing the Reset pushbutton. Pressing the Reset
pushbutton also sends the display back to the metering screen and clears the metering screen alarms
Human-Machine Interface