Summing point overexcitation limiter, Takeover overexcitation limiter, Underexcitation – Basler Electric DECS-400 User Manual
Page 176

164
9369700990 Rev R
Summing Point Overexcitation Limiter
Three on-line setpoint levels ...... 1 (high), 2 (medium), and 3 (low). Limiter response is less than 3 cycles.
Setpoint Range
Level 1, 2, 3 ............................ 0 to 11,999 Adc
Setpoint Increment
Level 1, 2, 3 ............................ 0.1% of the rated field current
Limiting Time Range
Level 1 .................................... 0 to 60 s
Level 2 .................................... 0 to 120 s
Level 3 .................................... Indefinite
Limiting Time Increment
Level 1, 2 ................................ 1 s
Level 3 .................................... N/A
Two off-line setpoint levels ............ 1 (high) and 2 (low). Limiter response is less than 3 cycles.
Setpoint Range
Level 1, 2 ................................ 0 to 11,999 Adc
Setpoint Increment
Level 1, 2 ................................ 0.1% of the rated field current
Limiting Time Range
Level 1 .................................... 0 to 60 s
Level 2 .................................... Indefinite
Limiting Time Increment
Level 1 .................................... 1 s
Level 2 .................................... N/A
Takeover Overexcitation Limiter
Two on-line setpoint levels ............ High and Low. Limiter response is less than 3 cycles.
Setpoint Range
High, Low Level ................ 0 to 11,999 Adc
Setpoint Increment
High, Low Level ................ 0.1 Adc
Time Dial
Range ............................... 0.1 to 20 s
Increment ......................... 0.1 s
Two off-line setpoint levels ............ High and Low. Limiter response is less than 3 cycles.
Setpoint Range
High, Low Level ................ 0 to 11,999 Adc
Setpoint Increment
High, Low Level ................ 0.1 Adc
Time Dial
Range ............................... 0.1 to 20 s
Increment ......................... 0.1 s
Underexcitation
User-selectable, summing-point type or takeover limiter. UEL curve is selected by specifying the
acceptable reactive power level at zero active power output or by entering a five-point UEL characteristic.
UEL adjusts characteristic according to changes in generator terminal voltage.
Reactive Power
Setting Range ......................... 0 to 41 kvar (leading)
Setting Increment.................... 1 kvar
Real Power
Setting Range ......................... 0 to 41 kW
Setting Increment.................... 1 kW
Specifications
DECS-400