Holding registers for operating mode parameters – Basler Electric DECS-400 User Manual
Page 229
9369700990 Rev R
217
Holding Registers for Operating Mode Parameters
Table 38. Information Category C4—Operating Mode Parameters
Registers
Data Description
Access
Data
Format
40601
Virtual toggle switch for changing unit mode from stop to start. Value 1 is
only valid to apply. Reading this register provides the status: 0=STOP,
1=START.
RW
UINT16
40602
Virtual toggle switch for changing control from AVR mode to Manual mode.
Value of 1 is the only valid value to apply. Reading this register provides the
control mode status: 0=base mode, 1=manual, 2=AVR.
RW
UINT16
40603
Virtual toggle switch for changing operation between unit and parallel.
Value 1 is only valid to apply. Read value of register is aloways 0.
RW
UINT16
40604
PF/Var Enabled 0=off, 1=PF, 2=var
RW
UINT16
40605
Internal Tracking Enabled
RW
UINT16
40606
Pre-position 1 Enabled
RW
UINT16
40607
Raise Enabled
RW
UINT16
40608
Lower Enabled
RW
UINT16
40609
LimiterMode; 0=off, 1=UEL, 2=OEL, 3=UEL&OEL, 4=SCL, 5=UEL&SCL,
6=OEL&SCL, 7=UEL&OEL&SCL, 8=VARL, 9=VARL&OEL,
10=VARL&OEL, 11=VARL&OEL&UEL, 12=VARL&SCL,
13=VARL&SCL&OEL, 14=VARL&SCL&OEL, 15=VARL&SCL&UEL&OEL
RW
UINT16
40610
Voltage Matching Mode (0=off, 1=on)
R
UINT16
40611
Operating Mode (0=off, 1=PF, 2=var)
R
UINT16
40612
Unit mode where 0=stop, 1=start
R
UINT16
40613
Control Mode (1 = Manual, 2 = AVR)
R
UINT16
40614
Internal Tracking Enabled
R
UINT16
40615
Pre-position Enabled
R
UINT16
40616
Auto Transfer Enabled
R
UINT16
40617
Load Comp Mode (0=off, 1=droop, 2=L droop, 4=CCC)
R
UINT16
40618
Alarm Reset Enabled
RW
UINT16
40619
Loss Of Sensing Mode
RW
UINT16
40620
No Sense To Manual Mode
RW
UINT16
40621
External Tracking Enabled
RW
UINT16
40622
Underfrequency Mode
RW
UINT16
40631
Droop Enabled
RW
UINT16
40632
L Drop Enabled
RW
UINT16
40633
CC Enabled
RW
UINT16
40634
OEL Style Mode
R
UINT16
40635
External Tracking Enabled
R
UINT16
40636
OEL Style Enabled
RW
UINT16
40637
Pre-position 2 Enabled
R
UINT16
40638
UEL Style Mode
R
UINT16
40639
OEL Option Mode
R
UINT16
40640
Pre-position Selection
R
UINT16
40641
UEL Style Enabled
RW
UINT16
40642
Voltage Matching Enabled
RW
UINT16
40643
OEL Enabled
RW
UINT16
40644
UEL Enabled
RW
UINT16
40645
SCL Enabled
RW
UINT16
40646
Internal Tracking Mode
R
UINT16
40647
External Tracking Mode
R
UINT16
40648
Voltage Matching Mode
R
UINT16
40649 to
40674
Reserved for future C4 use
R
Not
Defined
40675
Var limiter enable; 0=disable, 1=enable
RW
UINT16
40720
Enables traverse rate to pre-position 1 for the mode
RW
UINT16
40721
Enables traverse rate to pre-position 2 for the mode
RW
UINT16
40722
Enables traverse rate to pre-position 1 for the mode
RW
UINT16
40723
Enables traverse rate to pre-position 2 for the mode
RW
UINT16
40724
Enables traverse rate to pre-position 1 for the mode
RW
UINT16
40725
Enables traverse rate to the pre-position 2 for the mode
RW
UINT16
DECS-400
Modbus™ Communication