PF Mode
Status indication of PF (0=off, 1=on) (DECS-400 does not need to be in Start).
Note
FCR, AVR, VAR, and PF mode indicate the mode the regulator is
currently in. Only one of these four modes can be active at any time.
This is not an indication of which mode (PF or VAR) the regulator will
enter when the breaker is closed.
Droop Mode
Indication that the regulator is in droop mode.
Voltage Match
Indication of voltage matching (1=active).
Load Comp
0=offline, 1=online (directly follows the Parallel logic input).
Failed to Build Up
0=successful buildup, 1=failure (directly follows alarm).
Field Flashing
Flashing control (active for flash) (controls flashing contactor).
Soft Start
Indication of soft start (1=active) (active during flashing).
New Osc Record
A new osc record is available.
Gen Over Voltage
Indication of a generator overvoltage protection alarm.
Gen Under Voltage
Indication of a generator undervoltage protection alarm.
Field Over Voltage
Indication of a field overvoltage protection alarm.
Field Over Current
Indication of a field overcurrent protection alarm.
Field Over Temp
Indication of a field overtemperature protection alarm.
Loss of Field
Indication of a loss of field protection alarm.
Loss of Sensing
Indication of a loss of sensing protection alarm.