Holding registers for startup parameters – Basler Electric DECS-400 User Manual
Page 232

220
9369700990 Rev R
Registers
Data Description
Access
Data
Format
40839
Step size for PF mode setpoint's adjustable maximum (in % of rated field
current) = .005
R
FLOAT
40841
FCR mode setpoint pre-position 2; adjustment range is determined by
registers (40761-62) and (40769-70)
RW
FLOAT
40843
AVR mode setpoint pre-position 2; adjustment range is determined by
registers (40763-64) and (40771-72)
RW
FLOAT
40845
VAR mode setpoint pre-position 2; adjustment range is determined by
registers (40765-66) and (40773-74)
RW
FLOAT
40847
PF mode setpoint pre-position 2; adjustment range is determined by
registers (40767-68) and (40775-76)
RW
FLOAT
40849
Line Drop Compensation Setpoint, adjustable from 0 to 30% in .1%
increments
RW
FLOAT
40851
FVR mode setpoint (in volts). Adjustment range is determined by registers
40853-54 and 40855-56
RW
FLOAT
40853
FVR maximum setpoint (in volts). Equal to % of nominal x rated field
voltage (Registers 40863-64 x 40477-78
÷ 100)
R
FLOAT
40855
FVR maximum setpoint (in volts). Equal to % of nominal x rated field
voltage (Registers 40865-66 x 40477-78
÷ 100)
R
FLOAT
40857
FVR mode traverse rate, adjustable from 10 to 200 seconds in 1 second
increments
RW
FLOAT
40859
FVR mode setpoint pre-position 1 adjustment range. Determined by
registers (40853-54) and (40855-56)
RW
FLOAT
40861
FVR mode setpoint step size. =setpoint range
÷ (traverse rate x 10):[regs.
40855-56) –regs. 40853-54)]
÷[(regs. 40857-58) x 10]
R
FLOAT
40863
FVR mode setpoint minimum (in % of rated field voltage), adjustable from 0
to 100% in 0.1% increments
RW
FLOAT
40865
FVR mode setpoint maximum (in % of rated field voltage), adjustable from
100 to 120% in 0.1% increments
RW
FLOAT
40867
Minimum value for FVR mode setpoint’s adjustable minimum (in % of rated
field voltage) =0%
R
FLOAT
40869
Maximum value for FVR mode setpoint’s adjustable maximum (in % of
rated field voltage) = 120%
R
FLOAT
40871
Step size for FVR mode setpoint’s adjustable maximum (in % of rated field
voltage) = 0.1%
R
FLOAT
40873
FVR mode setpoint pre-position 2: adjustment range is determined by
registers (40853-54) and (40855-56)
RW
FLOAT
Holding Registers for Startup Parameters
Table 40. Information Category C6—Startup Parameters
Registers
Data Description
Access
Data
Format
41151
Active Startup Setting Group
R
UINT16
41153
PSS Power Level Enable
R
UINT16
41154 to
41170
Not used
R
Not
Defined
41171
Primary Generator Voltage Soft Start Bias
RW
FLOAT
41173
Primary Generator Voltage Soft Start Time
RW
FLOAT
41175
Underfrequency Setting (Corner Frequency)
RW
FLOAT
41177
V/Hz High Setting
RW
FLOAT
41179
V/Hz Low Setting
RW
FLOAT
41181
V/Hz Time Setting
RW
FLOAT
41183
Voltage Matching Band
RW
FLOAT
41185
Voltage Matching Level (Generator to Bus)
RW
FLOAT
41187
Fine Voltage Adjust Band
RW
FLOAT
41189
Loss of Sensing Time Delay
RW
FLOAT
Modbus™ Communication
DECS-400