beautypg.com

Basler Electric DECS-400 User Manual

Page 158

background image

146

9369700990 Rev R

Parallel the generator with the bus. ....................................................................................... ________

Set the machine kilowatts for approximately 25% of machine rating at zero vars. ............... ________

Check for a phase shift at the DECS-400 between the voltage sensing and current
sensing B-phase inputs. The B-phase current should lag the sensed voltage between
E1 and E3 by 90 degrees. ..................................................................................................... ________

If the phase relationship is correct, proceed with testing. If the phase relationship is
incorrect, troubleshoot the system, resolve the problem, and retest as appropriate
before transferring to AVR mode. .......................................................................................... ________

Verify that AVR is nulled to FCR. .......................................................................................... ________

Verify that all null status indicators provide the null indication. ............................................. ________

Verify that AVR Pre-Position mode is disabled or the external pre-position contacts are
open. ...................................................................................................................................... ________

In the following step, be prepared to transfer back to Manual mode if the excitation voltage increases
suddenly.

Transfer to AVR. .................................................................................................................... ________

OEL Test

Disable the overexcitation limiter through the Configuration tab of the BESTCOMS
Limiter screen. ....................................................................................................................... ________

Set the On-Line, OEL three current limits at 15% above the no-load field current with a
5 second time delay. .............................................................................................................. ________

Using the Analysis screen capabilities of BESTCOMS, prepare to check the OEL response time. If the
response time is too slow, increase OEL gain parameters Ki and Kg and repeat the test.

Increase the field excitation until the field current reaches 125% of the no-load field
current setting. ....................................................................................................................... ________

Enable OEL through the Configuration tab of the BESTCOMS Limiter screen. ................... ________

Verify that the response time is within specified limits. ......................................................... ________

Enter the final, operating OEL values. ................................................................................... ________

UEL Test

Disable the underexcitation limiter through the Configuration tab of the BESTCOMS
Limiter screen. ....................................................................................................................... ________

Set the UEL var limit for 5% vars into the generator. ............................................................ ________

Adjust the vars into the generator for 15% at 25% load. ....................................................... ________

Perform a step response into the UEL limit by enabling UEL in BESTCOMS. ..................... ________

Verify stable performance and speed of response. ............................................................... ________

If the response time is too slow, increase the UEL gain (Ki and Kg) and repeat the test.

Verify stable UEL performance by testing the machine from 25% through 100% real
power loading, underexcited. ................................................................................................. ________

Increase the excitation above the UEL limit. ......................................................................... ________

Enter the final, operating UEL values. ................................................................................... ________

SCL Test (If Applicable)

Disable stator current limiting through the Configuration tab of the BESTCOMS Limiter
screen. ................................................................................................................................... ________

Operate the unit at approximately 30% load at 0.8 lagging power factor in Droop mode. .... ________

Using BESTCOMS, set the SCL low limit to 5% greater than the metered current. ............. ________

Commissioning

DECS-400