3.8 Basic Initial Functional Test

CAUTION:

Work carefully when performing these tests; hazardous voltages are

present on the input and output during this test.

Refer to Figure 3-5 for the required functional test set up. Proceed as follows to perform a basic
function check of the power system:

1. Verify the correct AC line input rating on the nameplate and the AC line input selector switch at the

rear panel. Make sure the correct line voltage is selected before applying input power.

2. Connect a suitable resistive or other type load to the output of the unit. Suggested load values for

both voltage ranges are shown in Table 3-10. Make sure the power resistor has sufficient power
dissipation capability for full load test and that the load used does not exceed the maximum power
rating of the AC source.

3. Connect an oscilloscope and DMM / voltmeter to the AC source output. Set both for AC mode.

4. Turn on the power source using the On/Off switch on the front panel. Allow the power source to

initialize.

5. Set the output voltage to 0 volt and close the output relay with the OUTPUT ON/OFF button.

There should be little or no output although the DMM may show a noise level, especially if the
DMM is in auto ranging mode.

6. Select the Set screen and use the keypad to program a small voltage (20 VAC). Observe the DMM

reading. The reading should track the programmed voltage.

7. Also monitor the scope display. The output signal should be a sinusoidal voltage waveform.

8. If the output tracks, increase the voltage until you reach 115V on the low voltage range or 230V on

the high voltage range. Check the output voltage reading and waveform.

9. Select the measurement screen by pressing the Meas button. The output voltage, current and

power will be displayed.

In the unlikely event the power source does not pass the functional test, refer to the calibration
procedure in Section 6

or call California Instrument’s customer satisfaction department for further

assistance.

Model

115V on 150 V range

230V on 300 V range

751i/iX

20 Ohm

80 Ohm

1501i/iX

10 Ohm

40 Ohm

Table 3-10: Load Resistance