7.6.2 POWER BOARD

7.6.2.1 HIGH VOLTAGE DC INPUT

PINS

NAME

DESCRIPTION

E1

+250V_IN

+250 Vdc @ <5 Adc, must be able to sink current from module

E2

HV_COM_IN

Return for +/- 250V_IN

E3

-250V_IN

-250 Vdc @ <5 Adc, must be able to sink current from module

7.6.2.2 HIGH VOLTAGE OUTPUT

PINS

NAME

DESCRIPTION

E4

HV_COM_OUT

Return for E5 and E6

E5

OUTPUT_LEFT

0

– 150 Vac, 375 VA max from 120 Vac to 150 Vac, 3.13 Arms max

E6

OUTPUT_RIGHT

Same as for E5

7.6.3 CONFIGURATION

The module may be configured to operate as two independent 375 VA LO RANGE half bridges or as a
single 750 VA dual range half/full bridge. Because DIP switches are used to set the operation of each
power module, configuration may only be performed manually.

Note: Unless a module was exchanged in the field, the i/iX comes factory configured for the

correct mode of operation and these dip-switch settings should normally not have to be
changed. This information is provided for reference only.
Only factory authorized personnel should use this information if needed.

7.6.3.1 DIP SWITCH SETTINGS

DIP SWITCH S1

DIP switch S1 selects which oscillator phase will drive each half bridge.

DIP SWITCH
POSITION

NAME

FUNCTION

1

LA

ON for LEFT = Phase A (LB, LC must be OFF)

2

RA

ON for RIGHT = Phase A (RB, RC must be OFF)

3

LB

ON for LEFT = Phase B (LA, LC must be OFF)

4

RB

ON for RIGHT = Phase B (RA, RC must be OFF)

5

LC

ON for LEFT = Phase C (LA, LB must be OFF)

6

RC

ON for RIGHT = Phase C (RA, RB must be OFF)