7.3.3 Overload Light is On

CAUSE

SOLUTION

Unit is overloaded

Remove overload or check CL setting

Unit is switched to high voltage range.

Select correct voltage range.

7.3.4 Distorted Output

CAUSE

SOLUTION

Power source is grossly overloaded.

Reduce load

The crest factor of the load exceeds 3:1.

Reduce load current peaks by reducing
load.

7.3.5 No Output and No Lights on Front Panel

CAUSE

SOLUTION

Input switched off.

Switch unit on.

No input power.

Ensure power is present at AC input
terminal block.

Incorrect input voltage

230V applied to a unit configured for 115V
input. Check position of voltage selector
switch on rear panel.

7.3.6 No Output But Front Panel controller is active

CAUSE

SOLUTION

“OUTPUT ON” button is turned off.

Press OUTPUT ON so that “ON” LED is
lit.

Current limit programmed down or to zero.

Program current limit higher.

Voltage programmed down or to zero.

Turn amplitude control up.