Specifications, 1 electrical – AMETEK Compact i/iX Series User Manual
Page 13

User Manual
Compact i/iX Series
AMETEK Programmable Power
California Instruments
13
2. Specifications
Specifications shown are valid over an ambient temperature range of 25
5
C and apply after a 30
minute warm-up time. Unless otherwise noted, all specifications are per phase for sine wave output
into a resistive load. For three phase configurations or mode of operation, all specifications are for Line
to Neutral (L-N) and phase angle specifications are valid under balanced load conditions only.
Specifications for i models are identical to those for the iX except where noted.
2.1 Electrical
2.1.1 Input
– Series II
Note: Specifications apply at nominal AC line input voltage unless indicated otherwise.
Parameter
Specification
Model
751i / iX
1501i / iX
Line Voltage:
(single phase, 2 wire +
ground (PE))
115
– 230 VAC ± 10 %
(Universal input)
Line VA:
1050 VA / 1030 W
2000 VA / 1970 W
Line Current, full power:
< 8.9 Arms @ 115V
< 4.4 Arms @ 230V
< 17 Arms @ 115V
< 8.4 Arms @ 230V
Line Current at low line
input voltage, full power:
< 9.9 Arms @ 103.5V
< 4.8 Arms @ 207V
< 19.4 Arms @ 103.5V
< 9.3 Arms @ 207V
Line Frequency:
47-63 Hz
Efficiency (nominal line
input):
76 % (typical @ full load)
Power Factor:
0.98 (typical @ full load)
Power Factor at high line:
0.89 (typical @ full load)
Inrush Current:
180 Apk max.
Hold-Up Time:
> 10 ms
Isolation Voltage:
1350 VAC input to output
1350 VAC input to chassis