ADLINK ND-6067 User Manual
Page 267
![background image](/manuals/733481/267/background.png)
265
Calibration Procedure for ND-6013 Firmware Rev A3.05
1. Select the correct input range, different input range have
different apply calibration resistance.
2. Apply the correct offset resistance to the analog input
module ND-6013 channel 0, detail resistance value, see
table 9-3.
3. Send “Offset Calibration $(Addr)10” to analog input
module ND-6013 channel 0 .
4. Apply the correct span resistance to the analog input
module ND-6013 channel 0, detail resistance value, see
table 9-3.
5. Send “Span Calibration $(Addr)00” to analog input
module ND-6013 channel 0 .
6. Apply the correct offset resistance to the analog input
module ND-6013 channel 1, detail resistance value, see
table 9-3.
7. Send “Offset Calibration $(Addr)11” to analog input
module ND-6013 channel 1.
8. Apply the correct span resistance to the analog input
module ND-6013 channel 1, detail resistance value, see
table 9-3.
9. Send “Span Calibration $(Addr)01” to analog input
module ND-6013 channel 1.
10. Apply the correct offset resistance to the analog input
module ND-6013 channel 2, detail resistance value, see
table 9-3.
11. Send “Offset Calibration $(Addr)12” to analog input
module ND-6013 channel 2.
12. Apply the correct span resistance to the analog input
module ND-6013 channel 2, detail resistance value, see
table 9-3.
13. Send “Span Calibration $(Addr)02” to analog input
module ND-6013 channel 2 five times.
14. Repeat procedure 2 to procedure 13 two times.