beautypg.com

ADLINK ND-6067 User Manual

Page 148

background image

146

6.2.3 Read Module Name

@Description

Read NuDAM module‘s name.

@Syntax

$(Addr)M

$

Command leading code.

(Addr) Address

ID.

M

Read module name.

@Response

!(Addr)(ModuleName)

or

?(Addr)

!

Command is valid.

?

Command is invalid.

(Addr) Address

ID.

(ModuleName)

NuDAM module‘s name.

@Example

User command:

$30M

Response:

!306050

!

Command is valid

30 Address.
6050

ND-6050 (Digital I/O module).

(601x,602x,605x,60
6x,6080,6531)