Page 231

229
6.8.1 Read Command Leading Code Setting
@Description
Read command leading code setting and host watchdog status.
@Syntax
~(Addr)0
~
Command leading code.
(Addr) Address
ID
0
Read command leading code setting.
@Response
!(Addr)(Status)(C1)(C2)(C3)(C4)(C5)(C6)
or
?(Addr)
!
Command is valid.
?
Command is invalid.
(Addr) Address
ID
(Status) (2-character)
Bit 0 : Reserved
Bit 1 : Power failure or watchdog failure
Bit 2 : Host watchdog is enable
Bit 3 : Host failure
(C1)
Leading code 1, for read configuration status,
firmware version, etc. default is $. (1-character)
(C2)
Leading code 2, for read synchronize sampling, digital
output ,default is #. (1-character)
(C3)
Leading code 3, for change configuration.
default is %. (1-character)
(C4)
Leading code 4, for read alarm status, enable alarm,
etc. default is @. (1-character)
(C5)
Leading code 5, for read command leading code,
change command leading code, etc. default is ~.
(1-character)
(C6)
Leading code 6, this leading code is reserved. default
is *. (1-character)
@Example
User command:
~060
Response:
!0600$#%@~*
Command leading code setting is $#%@~* for module address ID is
06, current status is factory default setting.
(601x,602x,605x,