Input Range is Type T thermocouple (range -100
°C to 400°C)
♦
Input is -50.5
°C
engineering units:
-
050.50
Example 5:
♦
Output range is 0 to 20 mA
♦
Output value is +5.678 mA
The data value should be : 05.678
Example 6:
♦
Output range is 0 to 10 V
♦
Output value is +2.345 V
The data value should be : 02.345
8.2 Percent of FSR (Full Scale Range)
• Data format bit 1 and 0 set to 01 is percent of FSR
• This data format including three components
1. sign (+ or - )
2. digits
3. decimal point
• Data is sign (+ or - ) followed with 5-digits and a decimal
point
• It does not exceed 7-characters. Data string of analog
output modules is fixed length of 6 characters. The value is
composed of five decimal digits with a decimal fixed point.
• Analog input modules maximum resolution is 0.01%, and
the decimal point is fixed.Analog output modules maximum
resolution is 0.2%.
• Data is the ratio of input signal to the value of full scale range
The different analog input/output ranges have different
resolutions. Refer to Table 8-5 ,Table 8-6 and Table 8-7 for
details.