ADLINK ND-6067 User Manual
Page 139
137
@Example 2
User command:
%0118310610
Response:
!18
Item Meaning
Description
%
(Leading Code)
Command leading code.
01
(OldAddr)
Original address ID is 01(Hex).
18
(NewAddr)
New address ID is 18(Hex).
31 (OutputRange)
Analog
output range is 4 to 20 mA
06
(BaudRate)
Baud rate is 9600.
10
(DataFormat)
10 means a slew rate is 1.000 mA/sec
and checksum is disable.
return 0x0D.
Code
(Hex)
Signal Range of Output Range
Modules
30
0 to 20 mA
6021
31
4 to 20 mA
6021
32
0 to 10 V
6021
33
-10 to 10 V
6024
Table 6-2 Analog Output Range Setting
@Example 3
User command:
%0130400600
Response:
!30
Item Meaning
Description
%
(Leading Code)
Command leading code.
01
(OldAddr)
Original address ID is 01H.
30
(NewAddr)
New address ID is 30H (Hex).
40
(TypeCode)
Digital I/O module.
06
(BaudRate)
Baud rate is 9600.
00
(CheckSumFlag)
00 means checksum is disable.
return
0x0D.