ADLINK ND-6067 User Manual
Page 247
245
Initialization Procedure
1. Power off the host computer and the installed NuDAM-6520.
Be sure of the baud rate of the NuDAM-6520 is 9600 bps.
2. Connect a brand-new NuDAM module with the RS-485. Set
the module in Default State by shorting the DEFAULT* pin.
Refer to Figure 7-1 for detailed wiring.
3. Power on the host computer.
4. Power on the power supply for NuDAM modules.
5. Use the NuDAM Administration utility to configure the
address ID, Baud rate and check-sum status of the module.
Initialization Wiring
Figure 7-1 Layout for Initialization the NuDAM module
7.3 Install a New NuDAM to a Existing Network
Equipments for Install a New Module
• A existing NuDAM network
• New NuDAM modules
• Power supply (+10 to +30 V
DC
)
Installing Procedures
Host
Computer
DATA
+
DATA
-
DATA+
DATA -
Default*
Local Power Supply
+10 V to +30 V
New
NuDAM
module
NuDAM-6520
RS-232/RS-485
Converter
RS-23
+Vs GND
+Vs GND
+Vs