ADLINK ND-6067 User Manual
Page 175

173
6.4.10 Save Power On Analog Output Value
@Description
Save the current output value to the non-volatile register for
NuDAM analog output module. The power on value be put on
the output channel when system power ON.
@Syntax
$(Addr)4
$
Command leading code. (1-character)
(Addr)
Address ID. (2-character)
4
Function code of saving power on analog value.
(1-character)
@Response
!(Addr)
or
?(Addr)
!
Command is valid.
?
Command is invalid.
(Addr)
Address ID.
@Example
User command:
$064
Response:
!06
Save the current analog output value as the default value when the
analog output module start-up.
(602x)