ADLINK ND-6067 User Manual
Page 137
135
@Response
!(Addr)
or
?(Addr)
(Addr) Address
ID.
!
Command is valid.
?
Command is invalid, parameter values are invalid, or
change the setting without grounding the DEFAULT*
pin.
Note: When you want to change the checksum or baud rate,
the DEFAULT* pin must be grounded at first.
@Example 1
User command:
%0130050600
Response:
!30
Item Meaning
Description
%
(Leading Code)
Command leading code.
01
(OldAddr)
Original address ID is 01(Hex).
30
(NewAddr)
New address ID is 30(Hex).
05 (InputRange) Analog input range is
±2.5V
06
(BaudRate)
Baud rate is 9600.
00
(DataFormat)
00 means data format is engineering
units, checksum is disable and
integration time is 50 ms (60Hz).
return 0x0D.