ADLINK ND-6067 User Manual
Page 153

151
6.3.2 Offset Calibration to each Channel
@Description
To correct the offset errors of AD converter by using the offset
calibration.
@Syntax
$(Addr)1(Channel No)
$
Command leading code
(Addr)
Address ID
1 Offset
calibration.
(Channel No)
Channel for calibration.(1 character)0~2
@Response
!(Addr)
or
?(Addr)
!
Command is valid.
?
Command is invalid.
(Addr) Address
ID.
@Example
User command:
$0612
Response:
!06
To perform the offset calibration for analog input module
ND-6013 channel 2 at specified address 06 (Hex).
Note: To perform the calibration, a proper input signal should
be connected to the analog input module. Different
input range have different input voltage, detail refer
chapter 9 “Calibration” .
Note
(14)
: For 6013 F/W version A3.05~A4.60
(6013
(14)
)