ADLINK ND-6067 User Manual
Page 172
170
6.4.7 Trim Calibration
@Description
Trims the specified analog output module a specified number
of units up or down.
@Syntax
$(Addr)3(Counts)
$
Command leading code
(Addr) Address
ID
3
Function Code
(Counts)
Number of counts to increase or decrease the output
current.
Range 00 - 5F : 0 to +95 counts (increase)
Range A1 - FF : -95 to -1 counts (decrease)
1 count equals approximately 4.88
μA or 2.44mV
(4.88mV for ND-6024)
@Response
!(Addr)
or
?(Addr)
!
Command is valid.
?
Command is invalid.
(Addr) Address
ID.
@Example
User command:
$06314
Response:
!06
Increase analog output value about 97.6
μA (14H * 4.88μA = 97.6μA) at
address 06H.
Note : Analog output module trim calibration should have a
corrent calibration wiring. Refers to Chapter 9 “Analog
Output Calibration” for details.
(602x)