ADLINK ND-6067 User Manual
Page 101
![background image](/manuals/733481/101/background.png)
99
5.6.2 Specifications of NuDAM-6058
Interface
♦
Interface : RS-485, 2 wires
♦
Speed (bps) : 1200, 2400, 4800, 9600, 19.2K, 38.4K, 57.6K,
115.2K (115.2K is only for firmware reversion
above A4.00)
Programmable Digital Input/Output
♦
Channel numbers : 24
♦
Input Signal:
♦
Logical level 0: 0.8 V
max
♦
Logical level 1: 2.0 V
min.
♦
Output Signal:
♦
Logical level 0: 0.5 V
max.
♦
Logical level 1: 2.4 V
min.
Watchdog Function
♦
Module internal watchdog timer : 150msec
♦
Power failure threshold : 4.65 V
♦
Safe value : 15 output channels
♦
Host programmable watchdog :100 ms ~ 25.5 sec
Dedicated Digital Input
♦
Channel numbers : 4
♦
Input Signal:
♦
Logical level 0: -0.5~0 V
♦
Logical level 1: 3 V ~ 5.25 V
Connector
♦
10-pin skew terminal block
♦
50-pin SCSI II connector
Power
♦
Power supply : +10V to +30V
♦
Current consumption: 1.488 W