144

(DataFlag)

Current setting of module setting and
RS-232 configuration refer to Table 6-4
for details. (4-character, WXYZ)

6531

@Example 1

User command:

$302

Response:

!30050600

!

Command is valid.

30 Address

ID.

05

Analog input range is

±2.5 V.

06

Baud rate is 9600 bps.

00

checksum is disable.

@Example 2

User command:

$182

Response:

!18320610

!

Command is valid.

18 Address

ID.

32

Analog output range is 0 to 10V

06

Baud rate is 9600 bps.

10

The output data is in engineering units, slew rate is 1mA/sec,
checksum is disable.

@Example 3

User command:

$302

Response:

!30400600

!

Command is valid.

30 Address

ID.

40

Digital I/O module.

06

Baud rate is 9600 bps.

00

checksum is disable.