214
6.7.19 Set Minimum Input Signal Width at Low Level
@Description
Set the minimum input signal width at low level, for signal level low
less then this value will be filtered out as noise.
@Syntax
$(Addr)0L(MinFData)
$
Command leading code.
(Addr)
Address ID (2-character)
0L
Set minimum input signal width at low level command
code.
(MinFData)
The minimum width data at low level. The unit is
μs
and its resolution is 1
μs. This value range from 4 μs
to 1020
μs, which is a 4-digit integer. (4-character)
@Response
!(Addr)
or
?(Addr)
!
Command is valid.
?
Command is invalid.
(Addr) Address
ID.
@Example
User command:
$300L0010
Response:
!30
Item Meaning
Description
$
(Leading Code)
Command leading code.
30
(Addr)
Address ID is 30H.
0L
Set minimum input signal width.
0010 (MinFData)
10
μs
(6080)