EVCO S.p.A.
Vcolor 818
| Installer manual ver. 1.1 | Code 144VC818E114
page 75 of 94
(8)
if on activation of defrosting, the previous compressor switched on at from a time shorter than that established
with parameter d15, the compressor will remain on longer for the fraction of time necessary to complete this
time period
(9)
the temperature alarms are only enabled during storage
(10)
during defrosting, pre-dripping, dripping and evaporator fan standstill, the temperature alarms are not enabled,
on condition that they occurred after activation of defrosting. When the door is open, i.e. if the door micro
switch input is active and the parameter i0 is set at values different to 0, the maximum temperature alarm is
not enabled, on condition that occurred after the door was opened
(11)
if parameter P4 is set at 0, during pre-cooling, blast chilling and deep freezing the evaporator fan will be on and
during storing the device will operate as if parameter F2 it were set at 2
(12)
if parameter P5 is set at 0, the condenser fan will function parallel to the compressor
(13)
the door open is enabled only using the "run" state
(14)
if the door is opened during defrosting or evaporator fan standstill, opening has no effect on the compressor
(15)
modify the parameter during the "stand-by" status to prevent damage to the utility
(16)
the pump down valve is activated when the compressor is switched-on.