| Installer manual ver. 1.1 | Code 144VC818E114

page 71 of 94

F23

1

5

- - - -

5

speed at which the evaporator fan is switched on during

post blast chilling

1 = speed established with parameter F18 (speed 1)

2 = speed established with parameter F19 (speed 2)

3 = speed established with parameter F20 (speed 3)

4 = speed established with parameter F21 (speed 4)

5 = speed established with parameter F22 (speed 5)

F24

1

5

- - - -

5

speed at which the evaporator fan is switched on during

post deep freezing

1 = speed established with parameter F18 (speed 1)

2 = speed established with parameter F19 (speed 2)

3 = speed established with parameter F20 (speed 3)

4 = speed established with parameter F21 (speed 4)

5 = speed established with parameter F22 (speed 5)

F25

0

30

min

0

evaporator fan switch-on delay from compressor switch-on

on start-up of blast chilling and at the start-up of deep

freezing

Par.

Min.

Max.

Unit

Default

Digital inputs

i0

0

2

- - - -

2

effect caused by opening the door, i.e. by activation of the

door micro switch (13)

0 = no effect

1 = the compressor and the evaporator fan will be off

and the cabinet light will be on. On expiry of the

time established with parameter i2, the 3 digit

display will show the flashing “id” code and the

buzzer will be activated (until the door is closed);

see also parameter F15 (14)

2 = the evaporator fan will be off and the cabinet light

will be on. On expiry of the time established with

parameter i2, the 3 digit display will show the

flashing “id” code and the buzzer will be activated

(until the door is closed); see also parameter F15

i1

0

1

- - - -

0

type of door micro switch input contact

0 = normally open (input active with closed contact)

1 = normally closed (input active with open contact)

i2

-1

120

min

5

door open alarm signalling delay (“id” code); on expiry of

the time established with the parameter, the compressor

and the evaporator fan will be off

-1 = the alarm will not be signalled