F23
1
5
- - - -
5
speed at which the evaporator fan is switched on during
post blast chilling
1 = speed established with parameter F18 (speed 1)
2 = speed established with parameter F19 (speed 2)
3 = speed established with parameter F20 (speed 3)
4 = speed established with parameter F21 (speed 4)
5 = speed established with parameter F22 (speed 5)
F24
1
5
- - - -
5
speed at which the evaporator fan is switched on during
post deep freezing
1 = speed established with parameter F18 (speed 1)
2 = speed established with parameter F19 (speed 2)
3 = speed established with parameter F20 (speed 3)
4 = speed established with parameter F21 (speed 4)
5 = speed established with parameter F22 (speed 5)
F25
0
30
min
0
evaporator fan switch-on delay from compressor switch-on
on start-up of blast chilling and at the start-up of deep
freezing
Par.
Min.
Max.
Unit
Default
Digital inputs
i0
0
2
- - - -
2
effect caused by opening the door, i.e. by activation of the
door micro switch (13)
0 = no effect
1 = the compressor and the evaporator fan will be off
and the cabinet light will be on. On expiry of the
time established with parameter i2, the 3 digit
display will show the flashing “id” code and the
buzzer will be activated (until the door is closed);
see also parameter F15 (14)
2 = the evaporator fan will be off and the cabinet light
will be on. On expiry of the time established with
parameter i2, the 3 digit display will show the
flashing “id” code and the buzzer will be activated
(until the door is closed); see also parameter F15
i1
0
1
- - - -
0
type of door micro switch input contact
0 = normally open (input active with closed contact)
1 = normally closed (input active with open contact)
i2
-1
120
min
5
door open alarm signalling delay (“id” code); on expiry of
the time established with the parameter, the compressor
and the evaporator fan will be off
-1 = the alarm will not be signalled