If the test is completed successfully, the cycle will be started.
The maximum deep freezing duration count is started on condition that the temperature detected by the
needle probe is below that established with parameter r15.
5.2
If the test is not completed successfully, the buzzer will be activated for 5 s every 60 s and the cycle will
be started with timed-control; see paragraph 6.10 "Time-controlled soft deep freezing and storage".
During the soft deep freezing phase the device displays the temperature detected by the needle probe, the cabinet
temperature, the program name (if envisioned) and the time passed since the start of deep freezing.
Operate as indicated to stop the cycle:
6.
Press and hold the START/STOP key 3 s.
The successive parameters establish the following values:
-
parameter r3 establishes deep freezing soft phase end temperature.
-
parameter r6 establishes the maximum deep freezing duration
-
parameter r7 establishes the work set-point during the deep freezing soft phase.
When the temperature detected by the needle probe reaches the end temperature of the soft deep freezing phase, the
device automatically passes to deep freezing.
During deep freezing the device displays the temperature detected by the needle probe, the cabinet temperature, the
program name (if envisioned) and the time passed since the start of deep freezing.
The successive parameters establish the following values:
-
parameter r4 establishes the deep freezing end temperature
-
parameter r6 establishes the maximum deep freezing duration
-
parameter r8 establishes the work set-point during deep freezing.
If the temperature detected by the needle probe reaches the deep freezing end temperature within the maximum deep
freezing duration, it means that deep freezing has been completed successfully, the device will automatically pass to
storage and the buzzer will be activated for the period of time established with parameter AA.
Press and release a key to silence the buzzer.
During storage the device displays the temperature of the cabinet, the program name (if envisioned) and the time
taken to complete deep freezing successfully.