EVCO S.p.A.

Vcolor 818

| Installer manual ver. 1.1 | Code 144VC818E114

page 73 of 94

u6

1

240

min

5

switching on UV light for sterilisation cycle duration

u7

-99

199

°C/°F (1)

40

needle probe heating end temperature (temperature

detected by the needle probe); see also parameter u8

u8

0

240

min

2

maximum duration of needle probe heating; see also

parameter u7

0 = needle probe heating is disabled

u9

0

1

- - - -

1

needle probe heating on opening of the door, i.e. on

activation of the door entry micro switch, which occurs after

interruption of a blast chilling and storage cycle or a deep

freezing and storage cycle during storage.

1 = yes

u11

0

1

- - - -

0

utility managed by the output K7 (15)

0 = cabinet light (in this case, the DEEP FREEZING key

and parameters i0 will assume significance)

1 = UV light (in this case, the DEEP FREEZING key and

parameter u6 will assume significance)

u12

0

999

s

10

compressor switch off delay from pump down valve

deactivation (pump down in switch-off) (16)

Par.

Min.

Max.

Unit

Default

Serial

communication

(RS-48

serial

port

with

MODBUS communication protocol)

L0

0

1

- - - -

0

operating mode

0 = slave (in this case, it will be possible to connect

Parameters Manager set-up software system, to the

monitoring and surveillance system of the RICS

plants or to the data recording device, to download

the

recorded

data

to

the

port

(via

USB)

EVUSBREC01).

1 = master (in this case, it will be possible to connect the

print module PM 100A X9S001 to the port)

L1

1

240

min

5

print interval during blast chilling or during deep freezing

L2

1

240

min

15

print interval during storage

LA

1

247

- - - -

247

device address