EVCO EVCSR818P9EF User Manual

Page 65

background image

EVCO S.p.A.

Vcolor 818

| Installer manual ver. 1.1 | Code 144VC818E114

page 65 of 94

r12

-99

99

°C/°F (1)

5

work set-point during pre-cooling (cabinet temperature);

see also parameter r0

r13

-99

99

°C/°F (1)

15

end temperature of the temperature-controlled hard blast

chilling phase (temperature detected by the needle probe)

r14

10

100

%

60

duration of the time-controlled hard blast chilling phase

(intended as a percentage of the value established with

parameter r1); also duration of the time-controlled soft

deep freezing phase (intended as a percentage of the value

established with parameter r2)

r15

-99

199

°C/°F (1)

65

temperature below which the count of the maximum

temperature-controlled

blast

chilling

and

maximum

temperature-controlled

deep

freezing

is

started

(temperature detected by the needle probe)

r16

0

2

- - - -

1

type of operating cycle that can be selected

0 = blast chilling and storage

1 = blast chilling and storage or deep freezing and

storage

2 = deep freezing and storage

r17

0

99

°C/°F (1)

5

"temperature detected by the needle probe - cabinet

temperature" minimum difference such to consider the first

phase of the test to verify correct insertion of the needle

probe completed successfully (consider the difference

without sign)

0 = the test will not be performed (neither first or second

phase)

r18

1

99

10 s

20

duration of the second phase of the test for verification of

correct insertion of the needle probe

r19

- - - -

- - - -

- - - -

- - - -

reserved

r20

- - - -

- - - -

- - - -

- - - -

reserved

r22

- - - -

- - - -

- - - -

- - - -

reserved

r23

- - - -

- - - -

- - - -

- - - -

reserved

r40

- - - -

- - - -

- - - -

- - - -

reserved

r41

- - - -

- - - -

- - - -

- - - -

reserved

r42

- - - -

- - - -

- - - -

- - - -

reserved